Skip to content
Driven by technology and the environment. Heating systems for the future.
Contact us
Menu
Home/Products/WNS / CWNS

YINENG PRODUCTS

WNS/CWNS Oil/Gas-Fired Pressurized/Atmospheric Hot Water Boiler

Model / Series WNS / CWNS

A three-pass wet-back hot-water boiler, with CWNS atmospheric models rated 0.35–7 MW and WNS pressurized models rated 0.7–14 MW.

Atomized fuel burns in the corrugated furnace. Gas passes from the reversal chamber into the second-pass threaded tubes, turns at the front smokebox into third-pass plain tubes, then passes the rear smokebox, condensing economizer and chimney. Fully automatic intelligent controls are provided.

The tables separately list WNS pressurized and CWNS atmospheric hot-water models. Heat output and supply/return temperatures should be selected from the appropriate model table.

Design and features

Hinged smokebox

A hinged smokebox supports inspection and cleaning while improving sealing.

Corrugated furnace

Corrugations increase heating surface and disturb gas flow for heat transfer, improve furnace flexibility and strength, and reduce thermal-expansion stress.

Threaded smoke tubes

Threaded tubes increase heating area and flue-gas residence time within limited space. Heat-transfer performance is 1.3 times that of ordinary smoke tubes.

Condenser

Uses flue-gas heat to warm inlet water and lower exhaust temperature. Finned tubes and ND steel increase area and resist low-temperature corrosion.

Calculation basis: lower heating values of 8400 kcal/Nm³ for natural gas and 10250 kcal/kg for diesel. Y denotes oil firing and Q denotes gas firing.

PRODUCT DATA

Specifications

Pressurized hot water boilers

WNS Fully Automatic Oil/Gas-Fired Hot Water Boiler
Boiler model WNS0.7 WNS1.4 WNS2.1 WNS2.8 WNS4.2 WNS7.0 WNS10.5 WNS14
Rated heat output MW 0.7 1.4 2.1 2.8 4.2 7 10.5 14
Rated water outlet pressure MPa 1.0
Rated water outlet temperature ℃ 95/115
Rated return-water temperature ℃ 70
Boiler heating surface m2 25.6 46.3 69.3 92.2 141.2 220 344.2 426
Design thermal efficiency % 92.5 92.7 92.4 92.5 92.9 93.2 92.6 92.7
Design ambient temperature ℃ 20
Boiler net weight t 4.5 7.5 8.9 10.3 13.5 21 32.5 41
Boiler water capacity t 2.8 5.2 6.5 7.7 11.4 18.8 28.3 33.2
Combustion mode Slight-positive-pressure chamber combustion
Natural gas Nm3/h 75.5 151.5 224.2 298.2 450.2 751.8 1128.9 1502.6

Atmospheric hot water boilers

CWNS Fully Automatic Oil/Gas-Fired Atmospheric Hot Water Boiler
Boiler model CWNS0.35 CWNS0.7 CWNS1.05 CWNS1.4 CWNS2.1 CWNS2.8 CWNS4.2 CWNS7.0
Rated heat output MW 0.35 0.7 1.05 1.4 2.1 2.8 4.2 7
Rated water outlet temperature ℃ 85
Rated return-water temperature ℃ 60
Boiler heating surface m2 13.5 25.6 38.2 46.3 69.3 92.2 141.2 220
Design thermal efficiency % 92.4 92.5 92.6 92.7 92.4 92.5 92.9 92.8
Design ambient temperature ℃ 20
Boiler net weight t 3 3.9 4.2 5.8 7.8 9.1 11.2 21
Boiler water capacity t 2.2 2.9 3.2 4.8 6 8.5 9.6 18.8
Combustion mode Slight-positive-pressure chamber combustion
Natural gas Nm3/h 38 74.5 110.8 150.5 222.5 296.5 446.8 744.6