WNS Oil/Gas-Fired Condensing Steam Boiler

Model / Series WNS

A two-pass wet-back shell boiler with economizer and condenser. Evaporation is 1–20 t/h and design efficiency 100.2–100.5%.

Atomized fuel burns in the corrugated furnace and transfers radiant heat in the first pass. Gas turns in the reversal chamber into second-pass threaded smoke tubes, reaches the front smokebox and passes successively through the economizer and condenser before chimney discharge.

Design and features

Hinged smokebox

A hinged smokebox supports inspection and cleaning while improving sealing.

Corrugated furnace

Corrugations increase heating surface and disturb gas flow for heat transfer, improve furnace flexibility and strength, and reduce thermal-expansion stress.

Threaded smoke tubes

Threaded tubes increase heating area and flue-gas residence time within limited space. Heat-transfer performance is 1.3 times that of ordinary smoke tubes.

Condensing heat recovery

Recovers flue-gas heat to warm feedwater and reduce exhaust temperature. Finned tubes increase heating area; an ND-steel condenser resists low-temperature corrosion.

Calculation basis: lower heating values of 8400 kcal/Nm³ for natural gas and 10250 kcal/kg for diesel. Y denotes oil firing and Q denotes gas firing.

PRODUCT DATA

Specifications

WNS Fully Automatic Oil/Gas-Fired Condensing Steam Boiler
Boiler model WNS1 WNS1.5 WNS2 WNS3 WNS4 WNS6 WNS8 WNS10 WNS15 WNS20
Rated evaporation t/h 1 1.5 2 3 4 6 8 10 15 20
Rated steam pressure MPa 1.25(1.6)
Rated steam temperature ℃ 194(204)
Rated feedwater temperature ℃ 20 20(104)
Boiler body heating surface m2 19.3 27.9 36.5 54.8 62.3 112 125 165 237 290
Economizer heating surface m2 5.9 8.9 11.9 19.9 25.6 32.5 42.3 48.9 85.5 109
Condenser heating surface m2 7.9 13.9 19.9 25 32.2 43.6 56.6 81.9 150 192
Design thermal efficiency % 100.3 100.2 100.2 100.3 100.2 100.2 100.2 100.2 100.5 100.4
Design ambient temperature ℃ 20
Boiler net weight t 4.8 6.5 7.8 8.8 11.6 14.1 17.9 21.8 31 38
Boiler operating water capacity t 3.1 4 5.2 6.8 9 12.8 16.3 20.7 30.5 37.1
Boiler full-water capacity t 3.6 4.5 6.1 7.9 10.5 14.4 19.4 24.1 34.1 41
Boiler feedwater control On/off feedwater control Modulating feedwater control
Combustion mode Slight-positive-pressure chamber combustion
Natural gas Nm3/h 70.2 105.6 140.5 211.1 281.4 422.1 562.5 705.6 1055.4 1410.1
Diesel kg/h 60.4 90.2 121.4 181.1 239.5 362.1 479.6 601.5 902.8 1205.1
Transport dimensions Length mm 3850 4080 4250 4690 5250 6100 6210 6853 7430 7890
Width 1900 2000 2100 2350 2540 2600 2920 3110 3550 3750
Height 2110 2240 2450 2580 2800 2980 3280 3460 3800 4050
Installation dimensions Length mm 4630 4750 5100 5680 6350 7450 7700 8230 9380 9700
Width 2800 2990 3000 3250 3440 3500 3820 4010 4350 4550
Height 3200 3560 3720 3850 4120 4350 5000 5200 5600 6100
Feedwater connection DN mm 32 32 40 40 40 40 50 50 65 65
Main steam outlet DN mm 50 65 100 80 100 125 150 150 200 200