YINENG PRODUCTS
WNS/CWNS Oil/Gas-Fired Pressurized/Atmospheric Hot Water Boiler
Model / Series WNS / CWNS
A three-pass wet-back hot-water boiler, with CWNS atmospheric models rated 0.35–7 MW and WNS pressurized models rated 0.7–14 MW.
Atomized fuel burns in the corrugated furnace. Gas passes from the reversal chamber into the second-pass threaded tubes, turns at the front smokebox into third-pass plain tubes, then passes the rear smokebox, condensing economizer and chimney. Fully automatic intelligent controls are provided.
The tables separately list WNS pressurized and CWNS atmospheric hot-water models. Heat output and supply/return temperatures should be selected from the appropriate model table.
Design and features
Hinged smokebox
A hinged smokebox supports inspection and cleaning while improving sealing.
Corrugated furnace
Corrugations increase heating surface and disturb gas flow for heat transfer, improve furnace flexibility and strength, and reduce thermal-expansion stress.
Threaded smoke tubes
Threaded tubes increase heating area and flue-gas residence time within limited space. Heat-transfer performance is 1.3 times that of ordinary smoke tubes.
Condenser
Uses flue-gas heat to warm inlet water and lower exhaust temperature. Finned tubes and ND steel increase area and resist low-temperature corrosion.
Calculation basis: lower heating values of 8400 kcal/Nm³ for natural gas and 10250 kcal/kg for diesel. Y denotes oil firing and Q denotes gas firing.
PRODUCT DATA
Specifications
Pressurized hot water boilers
| WNS Fully Automatic Oil/Gas-Fired Hot Water Boiler | |||||||||
| Boiler model | WNS0.7 | WNS1.4 | WNS2.1 | WNS2.8 | WNS4.2 | WNS7.0 | WNS10.5 | WNS14 | |
| Rated heat output | MW | 0.7 | 1.4 | 2.1 | 2.8 | 4.2 | 7 | 10.5 | 14 |
| Rated water outlet pressure | MPa | 1.0 | |||||||
| Rated water outlet temperature | ℃ | 95/115 | |||||||
| Rated return-water temperature | ℃ | 70 | |||||||
| Boiler heating surface | m2 | 25.6 | 46.3 | 69.3 | 92.2 | 141.2 | 220 | 344.2 | 426 |
| Design thermal efficiency | % | 92.5 | 92.7 | 92.4 | 92.5 | 92.9 | 93.2 | 92.6 | 92.7 |
| Design ambient temperature | ℃ | 20 | |||||||
| Boiler net weight | t | 4.5 | 7.5 | 8.9 | 10.3 | 13.5 | 21 | 32.5 | 41 |
| Boiler water capacity | t | 2.8 | 5.2 | 6.5 | 7.7 | 11.4 | 18.8 | 28.3 | 33.2 |
| Combustion mode | Slight-positive-pressure chamber combustion | ||||||||
| Natural gas | Nm3/h | 75.5 | 151.5 | 224.2 | 298.2 | 450.2 | 751.8 | 1128.9 | 1502.6 |
Atmospheric hot water boilers
| CWNS Fully Automatic Oil/Gas-Fired Atmospheric Hot Water Boiler | |||||||||
| Boiler model | CWNS0.35 | CWNS0.7 | CWNS1.05 | CWNS1.4 | CWNS2.1 | CWNS2.8 | CWNS4.2 | CWNS7.0 | |
| Rated heat output | MW | 0.35 | 0.7 | 1.05 | 1.4 | 2.1 | 2.8 | 4.2 | 7 |
| Rated water outlet temperature | ℃ | 85 | |||||||
| Rated return-water temperature | ℃ | 60 | |||||||
| Boiler heating surface | m2 | 13.5 | 25.6 | 38.2 | 46.3 | 69.3 | 92.2 | 141.2 | 220 |
| Design thermal efficiency | % | 92.4 | 92.5 | 92.6 | 92.7 | 92.4 | 92.5 | 92.9 | 92.8 |
| Design ambient temperature | ℃ | 20 | |||||||
| Boiler net weight | t | 3 | 3.9 | 4.2 | 5.8 | 7.8 | 9.1 | 11.2 | 21 |
| Boiler water capacity | t | 2.2 | 2.9 | 3.2 | 4.8 | 6 | 8.5 | 9.6 | 18.8 |
| Combustion mode | Slight-positive-pressure chamber combustion | ||||||||
| Natural gas | Nm3/h | 38 | 74.5 | 110.8 | 150.5 | 222.5 | 296.5 | 446.8 | 744.6 |
Related products

WNS Oil/Gas-Fired Energy-Saving Steam Boiler
A three-pass wet-back shell boiler with an economizer for flue-gas heat recovery. Evaporation is 1–20 t/h and design efficiency 92.2–93.2%.
View product
WNS Oil/Gas-Fired Condensing Steam Boiler
A two-pass wet-back shell boiler with economizer and condenser. Evaporation is 1–20 t/h and design efficiency 100.2–100.5%.
View product
SZS Oil/Gas-Fired Saturated Steam Boiler
Longitudinal twin-drum D-type membrane-wall boiler, with evaporation of 10–50 t/h and design efficiency 92.8–93.2%.
View product