Skip to content
Driven by technology and the environment. Heating systems for the future.
Contact us
Menu

YINENG PRODUCTS

Electric Thermal Oil Boiler

Model / Series YDW

Electric heating bundles heat thermal oil circulated to process equipment. Outputs span 9–2400 kW, with efficiency ≥98%.

The YDW series uses thermal oil to provide high-temperature heat at low operating pressure. Bundled stainless-steel electric heating tubes are available in explosion-proof configurations.

Heating, controls, circulation, oil/gas separation and replenishment/expansion systems are integrated on one skid. A hot-oil pump supplies one or more heat users; the oil then returns for reheating and recirculation.

Design and features

316L heating bundle

316L stainless-steel elements support corrosion resistance, conversion efficiency and service life.

Interlocks and pressure relief

Circulation-pump interlocks, flow monitoring and remote transmission, pipeline explosion protection, supply/return temperature indication and transmission, power switching and a hot-oil bypass relief circuit.

Automatic control and communications

Microcomputer control or optional PLC with RS485, automatic temperature regulation, reserved DCS interface, remote app monitoring and flow, pressure and temperature interlocks; unattended operation can be configured.

Electrical controls and packaging

An isolated control cabinet supports component life. Electrical components include OMRON, FUJI, TE, LG, MOELLER, ABB, SIEMENS and JUMO. The inspected boiler is packaged for transport and commissioning.

PRODUCT DATA

Specifications

Detailed model designation: YDW- rated heat output (KW) KW
Rated heat output KW 9 30 60 90 120 160 180 240 300 360
X104Kcal/h 0.8 2.5 5 8 10 13 16 20 25 30
Thermal efficiency (Q) ≥% 98
Design pressure Mpa 1.0
Maximum medium temperature ℃ 320
Thermal oil circulation flow m3/h 3 12.5 12.5 25 25 30 30 100 100 100
Oil volume in heater m3 0.006 0.025 0.05 0.11 0.11 0.11 0.13 1 1.04 1.18
Pipe connection nominal diameter DN 25 50 50 50 50 65 65 150 150 150
Total installed system power KW 10.5 34.5 64.5 97 127 169 189 1223.5 1423.5 1623.5
Transport dimensions (length) mm 1460 1950 1840 1840 1840 2000 2160 2550 3800 3800
Transport dimensions (width) mm 925 485 485 485 950 1137 1139 2000 1400 1400
Transport dimensions (height) mm 778 1387 1874 2064 1882 1636 1387 2450 2450 2450
Total equipment weight Kg 155 344 421 555 716 768 846 3600 3850 4210
Continued
Rated heat output KW 480 720 750 1000 1200 1400 1600 1800 2000 2400
X104Kcal/h 40 60 63 80 100 120 135 150 160 200
Thermal efficiency (Q) ≥% 98
Design pressure Mpa 1.0
Maximum medium temperature ℃ 320
Thermal oil circulation flow m3/h 50 50 50 50 80 80 100 160 160 160
Oil volume in heater m3 0.21 0.3 0.35 0.48 0.55 0.55 0.9 1.33 1.49 1.77
Pipe connection nominal diameter DN 65 80 80 80 100 100 125 150 150 150
Total installed system power KW 256.5 316.5 376.5 496.5 743.5 773.5 1023.5 1838.5 2038.5 2438.5
Transport dimensions (length) mm 2180 2350 2180 2230 2500 2500 3320 3500 3500 3500
Transport dimensions (width) mm 1120 1330 1120 1460 1500 1500 1770 2000 2000 2000
Transport dimensions (height) mm 2086 2100 2427 1990 2104 2104 2200 2100 2550 2550
Total equipment weight (Kg) 1168 1390 2162 2305 2900 2900 3184 4750 5100 5500